Specification via analog values
To specify the setpoint via analog values, you can select the following for P100:
- Bipolar (processing of signed value of analog input 1 or fixed setpoint)
- Unipolar (processing of absolute value of analog input 1 or fixed setpoint)
- Motor potentiometer (virtual potentiometer)
- Fixed setpoint + AI1 (sum of selected fixed setpoint and value of analog input AI1 → P112 AI1 operating mode also applies)
- Fixed setpoint × AI1 (evaluation factor for analog input AI1→ 0 - 10 V = 0 - 100%)
- Bipolar AI2 (analog input 2 or fixed setpoint)