NF line filters
- Using the NF line filter, you can maintain limit value class C1/B with MOVITRAC® B sizes 0 to 5.
- NOTICE Possible damage to property
- Damage to the input level.
- No switching is permitted between the line filter and MOVITRAC® B.
- Install the line filter close to the inverter but outside the minimum clearance for cooling.
- Restrict the cable between the line filter and the inverter to the absolute minimum length required, and never more than 400 mm (15.7 in). Unshielded, twisted cables are sufficient.
- Use unshielded cables for the supply system connection as well.