NF line filters

  • Using the NF line filter, you can maintain limit value class C1/B with MOVITRAC® B sizes 0 to 5.
  • NOTICE Possible damage to property
  • Damage to the input level.
    • No switching is permitted between the line filter and MOVITRAC® B.
  • Install the line filter close to the inverter but outside the minimum clearance for cooling.
  • Restrict the cable between the line filter and the inverter to the absolute minimum length required, and never more than 400 mm (15.7 in). Unshielded, twisted cables are sufficient.
  • Use unshielded cables for the supply system connection as well.

Connecting NF line filters