Error 145 – Power and Energy Solutions extended

Error: 145.1 (9101hex | 37121dec)

Description: No FCB request possible with output stage enable

 

 

Cause

Measure

The switching status of the storage unit is unknown. This can be due to the following reasons:

– The switching status has not yet been determined because the MOVI-C® CONTROLLER has been restarted.

– A disconnection synchronization process has been terminated prematurely.

Re-select "DC synchronization" operating mode again and connect or disconnect the storage unit.

Error: 145.2 (9102hex | 37122dec)

Description: Inconsistent charging status control voltage limits

 

 

Cause

Measure

The voltage limit parameters have not been parameterized in ascending order from 4 to 1.

Correct the parameters in MOVISUITE® under [Operating modes] > [Charge status control] and update the configuration data.

Error: 145.16 (9110hex | 37136dec)

Description: At least one axis group member signals an error

 

 

Cause

Measure

At least one subordinate axis group member signals an error.

– Rectify the error.

– Perform a reset.

Error: 145.21 (9115hex | 37141dec)

Description: At least one axis group member signals an error

 

 

Cause

Measure

At least one subordinate axis group member signals an error.

– Rectify the error.

– Perform a reset.

Error: 145.32 (9120hex | 37152dec)

Description: An MRCD alarm has been triggered

 

 

Cause

Measure

The feedback contact to the IO module has poor contact or a wire break.

Check the signal cable from the MRCD to the IO module.

The fault current in the energy storage unit is greater than the alarm threshold.

Check the energy storage unit for ground fault. More information about this can be found in the user manual.

Error: 145.34 (9122hex | 37154dec)

Description: Function block "IOConnectorMRCD" not linked

 

 

Cause

Measure

The function block "IOConnectorMRCD" for exchanging the DIO signals has not been linked.

Link the function block correctly. More information about this can be found in the manual.

Error: 145.35 (9123hex | 37155dec)

Description: The "IOConnectorMRCD" function block is signaling a communication error

 

 

Cause

Measure

The interface to the "LogicalDevice" of the IO module has not been linked.

– Program the link.

or

– Disable the checking via Property.

The SBusPLUS communication is faulty and the IO module which supplies the values is not accessible.

– Check the SBusPLUS communication.

– Check the cabling of the SBusPLUS.

Error: 145.37 (9125hex | 37157dec)

Description: MRCD test failed

 

 

Cause

Measure

A wiring problem is present.

Check the cabling between MRCD and IO module.

An MRCD hardware defect is present.

Contact SEW-EURODRIVE Service.

Error: 145.64 (9140hex | 37184dec)

Description: Error Manager message list is full

 

 

Cause

Measure

A large number of error messages have occurred simultaneously.

– Rectify the error.

– Perform a reset.

Error: 145.65 (9141hex | 37185dec)

Description: Escalation to highest error response because an error was detected during the current error response

 

 

Cause

Measure

An error has occurred during the current error response (e.g. an error in the storage disconnection). A higher error response is selected to make escalation possible.

– Rectify the error.

– Perform a reset.

Error: 145.66 (9142hex | 37186dec)

Description: Test error reaction 10

 

 

Cause

Measure

A test error with reaction 10 has been triggered.

When the test has taken place, reset the error.

Error: 145.67 (9143hex | 37187dec)

Description: Test error reaction 20

 

 

Cause

Measure

A test error with reaction 20 has been triggered.

When the test has taken place, reset the error.

Error: 145.68 (9144hex | 37188dec)

Description: Test error reaction 30

 

 

Cause

Measure

A test error with reaction 30 has been triggered.

When the test has taken place, reset the error.

Error: 145.69 (9145hex | 37189dec)

Description: Test error reaction 40

 

 

Cause

Measure

A test error with reaction 40 has been triggered.

When the test has taken place, reset the error.

Error: 145.96 (9160hex | 37216dec)

Description: Parameter error: Output stage side to which energy storage unit has been connected has not been selected in the device

 

 

Cause

Measure

Error in parameter communication with MOVISUITE®.

Under [Data management] in the controller configuration in MOVISUITE®, download the data using "Update configuration data".

Error: 145.97 (9161hex | 37217dec)

Description: Relay and feedback contact of "Inrush Current Limiter" not connected

 

 

Cause

Measure

The fault can be caused as follows:

– Relay and feedback contact not configured.

– No external terminal function block configured.

– Configure relay and feedback contact in MOVISUITE® under [Device Functions] > [Inputs/Outputs].

or

– Configure external terminal function block.

Error: 145.98 (9162hex | 37218dec)

Description: Precharging fault

 

 

Cause

Measure

The fault can be caused as follows:

– Voltage via the dropping resistor does not drop.

– Voltage via the dropping resistor drops too slowly.

Check jumper relay.

Error: 145.99 (9163hex | 37219dec)

Description: Fault at jumper relay

 

 

Cause

Measure

Jumper relay is open and should be closed.

Check jumper relay.