Process input data (F-PI) substitute values

For all process data (F-PI) outgoing from the safety option, the value "0" is written as the substitute value. One exception is Fault state. For Fault state, the value "1" is written as the substitute value in the case of a fault-free protocol. In the case of a faulty F-protocol, the value "0" is written for Fault State.