Connecting supply system cables
Observe the following information when connecting the supply system cables:
- The nominal voltage and frequency of the device must correspond with the data of the supply system.
- Dimension the cable cross section according to the input current Iline for rated power (see product manual, chapter "Technical data").
- Install safety equipment F11/F12/F13 for line fuses at the beginning of the supply system cable behind the supply bus junction, see chapter "Wiring diagram".
- Dimension the safety equipment according to the cable cross section.
- When selecting the fuse, observe the information in the product manual > chapter "Technical data".
- Use only copper conductors with a permitted minimum temperature of 75 °C as connection cables.