Fault 48 Module bus

Error: 48.1 (3001hex | 12289dec)

Description: Incompatible device combination

 

Response: Output stage inhibit

Cause

Measure

Module bus stations are not compatible with one another.

Contact SEW‑EURODRIVE Service.

Error: 48.2 (3002hex | 12290dec)

Description: Communication timeout

 

Response: Emergency stop + output stage inhibit

Cause

Measure

Communication timeout on the module bus.

– Check the cable connections and voltage supply of the module bus stations.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Error: 48.3 (3003hex | 12291dec)

Description: Too many module bus stations

 

Response: Output stage inhibit

Cause

Measure

Too many module stations are connected.

Reduce the number of module bus stations.

Error: 48.4 (3004hex | 12292dec)

Description: CRC error

 

Response: Emergency stop + output stage inhibit

Cause

Measure

Checksum error detected during module bus communication.

– Switch the device off and on again.

– Reset the fault.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.