Communication between RobotMonitor and MOVI-C® CONTROLLER not possible

 

 

Problem

Communication between the RobotMonitor and the MOVI-C® CONTROLLER is not possible. The message "NO Communication" is displayed.

Remedy
  1. Check if "Start Communication" has been pressed.
  2. Check if the set IP address of the MOVI-C® CONTROLLER is correct. You can find the set IP address in MOVISUITE® or in the IEC Editor.
  3. Open the global variable list SEW_GVL_Internal in the IEC Editor.
  4. Navigate to the HMI_MyRobot variable ("MyRobot" corresponds to the name of the robot node that has been defined in MOVISUITE®).
  5. Check this variable and the subordinate blocks fbSimu3D, fbMonitor, and fbProgramEditor for error messages.
  6. In the device tree of the IEC Editor, double-click the object Device.
  7. Open the "Log" tab.
  8. Select the entry "MOS" as logger.
  9. Click the [Update] button.
  10. Check the messages for errors coming from the communication module of the software module, and eliminate the cause.
    • If the RobotMonitor is still not connected, contact SEW‑EURODRIVE Service.