Communication between RobotMonitor and MOVI-C® CONTROLLER not possible
Problem
Communication between the RobotMonitor and the MOVI-C® CONTROLLER is not possible. The message "NO Communication" is displayed.
Remedy
- Check if "Start Communication" has been pressed.
- Check if the set IP address of the MOVI-C® CONTROLLER is correct. You can find the set IP address in MOVISUITE® or in the IEC Editor.
- Open the global variable list SEW_GVL_Internal in the IEC Editor.
- Navigate to the HMI_MyRobot variable ("MyRobot" corresponds to the name of the robot node that has been defined in MOVISUITE®).
- Check this variable and the subordinate blocks fbSimu3D, fbMonitor, and fbProgramEditor for error messages.
- In the device tree of the IEC Editor, double-click the object Device.
- Open the "Log" tab.
- Select the entry "MOS" as logger.
- Click the [Update] button.
- Check the messages for errors coming from the communication module of the software module, and eliminate the cause.
- If the RobotMonitor is still not connected, contact SEW‑EURODRIVE Service.