Examples of the CTT2 Data Exchange Request/Response service
Access to the drive parameters of the decentralized inverter via the CTT2 "Data Exchange Request/Response" service is explained in more detail with a few examples.
A sample project can be found on the SEW‑EURODRIVE website (www.sew-eurodrive.com). Select [Online Support] > [Data & Documents] > [Software] and search for "TIA sample project".
The following figure shows the general process:

[1] | PLC |
[2] | AS‑Interface master |
[3] | B device |
[4] | Data Exchange Request message – This is sent to the B device with the parameter access data. |
[5] | Cyclic data exchange |
[6] | Acyclic parameter communication from the AS-Interface master to the B device consisting of:
|
[7] | Data Exchange Response message – This is sent to the AS-Interface master after the SPA Request message has been processed. |
[8] | Acyclic parameter communication from the B device to the AS-Interface master consisting of:
|
[9] | Data Exchange Response message – Contains the result of the parameter access in the SPA Response message. |