Error 31 thermal motor contactor
Subfault: 31.1 Description: Temperature sensor motor 1 – wire break | ||
---|---|---|
| Response: Application stop + output stage inhibit | |
Cause | Measure | |
Wire break detected at the temperature sensor of the motor. | Check the wiring of the temperature sensor. |
Subfault: 31.2 Description: Temperature sensor motor 1 – short circuit | ||
---|---|---|
| Response: Application stop + output stage inhibit | |
Cause | Measure | |
Short circuit at temperature sensor of motor. | Check the wiring of the temperature sensor. |
Subfault: 31.3 Description: Temperature sensor motor 1 – overtemperature | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
The motor temperature determined by the temperature sensor exceeds the maximum permitted motor temperature. | – Let the motor cool down. – Check for motor overload. – Check if the correct temperature sensor was configured. |
Subfault: 31.4 Description: Temperature model motor 1 – overtemperature | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
The motor temperature determined by the temperature model exceeds the maximum permitted motor temperature. | – Let the motor cool down. – Check for motor overload. – Check if the correct temperature sensor was configured. |
Subfault: 31.5 Description: Temperature sensor motor 1 – prewarning | ||
---|---|---|
| Response: Thermal motor protection 1 – prewarning threshold | |
Cause | Measure | |
Motor temperature determined via temperature sensor exceeded prewarning threshold. | Check for motor overload. |
Subfault: 31.6 Description: Temperature model motor 1 – prewarning | ||
---|---|---|
| Response: Thermal motor protection 1 – prewarning threshold | |
Cause | Measure | |
Motor temperature determined via motor model exceeded prewarning threshold. | Check for motor overload. |
Subfault: 31.7 Description: UL temperature model – overtemperature | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
The temperature of the active motor determined via the UL temperature model exceeds the maximum permitted motor temperature. | Check for motor overload. |
Subfault: 31.8 Description: Temperature sensor motor 1 – communication timeout | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Communication with temperature sensor is disrupted (e.g. via MOVILINK® DDI). | Check the wiring of the temperature sensor. |
Subfault: 31.9 Description: Temperature sensor motor 1 – temperature too low | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Short circuit in the long connection to the temperature sensor of the motor. | Check the wiring of the temperature sensor. | |
Temperature detected by temperature sensor fell below -50 °C. | – Check if the correct temperature sensor was configured. – Heat up the motor. |
Subfault: 31.11 Description: Temperature sensor motor 2 – wire break | ||
---|---|---|
| Response: Application stop + output stage inhibit | |
Cause | Measure | |
Wire break detected at the temperature sensor of the motor. | Check the wiring of the temperature sensor. |
Subfault: 31.12 Description: Temperature sensor motor 2 – short circuit | ||
---|---|---|
| Response: Application stop + output stage inhibit | |
Cause | Measure | |
Short circuit at temperature sensor of motor. | Check the wiring of the temperature sensor. |
Subfault: 31.13 Description: Temperature sensor motor 2 – overtemperature | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
The motor temperature determined by the temperature sensor exceeds the maximum permitted motor temperature. | – Let the motor cool down. – Check for motor overload. – Check if the correct temperature sensor was configured. |
Subfault: 31.14 Description: Temperature model motor 2 – overtemperature | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
The motor temperature determined by the temperature model exceeds the maximum permitted motor temperature. | – Let the motor cool down. – Check for motor overload. – Check if the correct temperature sensor was configured. |
Subfault: 31.15 Description: Temperature sensor motor 2 – prewarning | ||
---|---|---|
| Response: No response | |
Cause | Measure | |
Motor temperature determined via temperature sensor exceeded prewarning threshold. | Check for motor overload. |
Subfault: 31.16 Description: Temperature model motor 2 – prewarning | ||
---|---|---|
| Response: No response | |
Cause | Measure | |
Motor temperature determined via motor model exceeded prewarning threshold. | Check for motor overload. |
Subfault: 31.19 Description: Temperature sensor motor 2 – temperature too low | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Short circuit in the long connection to the temperature sensor of the motor. | Check the wiring of the temperature sensor. | |
Temperature detected by temperature sensor fell below -50 °C. | – Check if the correct temperature sensor was configured. – Heat up the motor. |
Subfault: 31.50 Description: Fault at temperature sensor 1 | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Fault detected at temperature sensor 1 of the motor. | Observe the error code of the main component. Obtain the exact cause of the error from this error message and take the appropriate fault elimination measures. |
Subfault: 31.51 Description: Fault at temperature sensor 2 | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Fault detected at temperature sensor 2 of the motor. | Observe the error code of the main component. Obtain the exact cause of the error from this error message and take the appropriate fault elimination measures. |
Subfault: 31.52 Description: Fault at temperature sensor 3 | ||
---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Fault detected at temperature sensor 3 of the motor. | Observe the error code of the main component. Obtain the exact cause of the error from this error message and take the appropriate fault elimination measures. |