Installing line choke

Observe the following information:

  • Install the choke close to the inverter but outside the minimum clearance for cooling. The choke must not be heated up by the exhaust air of the inverter.
  • Install the choke at the positions shown in the connection diagrams, see chapter Connection diagrams.
  • Observe the following minimum distances and mounting positions for convection cooling:

Permitted
mounting position

Distance in mm

On the side

Downwards

Upwards

1, 2, 3, 4

0

100

100

  • Observe the following permitted mounting positions during installation: