Step 3
- If the energy storage system is discharged to < 2 V, you can use the short circuit connector X5 on the socket contact X2 to prevent the energy storage system from recharging.
- It is absolutely necessary to connect the short-circuit connector so that voltage cannot accumulate again on the double-layer capacitor. The F10 fuse must always be ON so that the short circuit is ensured.
- For the UL variant, additionally check at the two measuring points on the front of the discharge connection unit that the energy storage unit is de-energized.