Installing the line choke

Observe the following information:

  • Install the line choke close to the regenerative power supply but outside the minimum clearance for cooling. The line choke must not be heated by the exhaust air of the regenerative power supply.
  • Install the choke at the positions shown in the connection diagrams, see chapter Connection diagrams.
  • Observe the following minimum distances and mounting positions for convection cooling:

Permitted
mounting position

Distance in mm

On the side

Downwards

Upwards

1, 2, 3, 4

0

100

100

  • Observe the following permitted mounting positions during installation: