Installing the line choke
Observe the following information:
- Install the line choke close to the regenerative power supply but outside the minimum clearance for cooling. The line choke must not be heated by the exhaust air of the regenerative power supply.
- Install the choke at the positions shown in the connection diagrams, see chapter Connection diagrams.
- Observe the following minimum distances and mounting positions for convection cooling:
Permitted | Distance in mm | ||
|---|---|---|---|
On the side | Downwards | Upwards | |
1, 2, 3, 4 | 0 | 100 | 100 |
- Observe the following permitted mounting positions during installation: