Process sequence and signal states
For information on the drive's behavior at standstill, refer to the specifications for the "Stop functions" in the "Functions" > "Monitoring functions" > "Control functions" configuration menu of the inverter.
No. | Sequence | PD | Signal states |
|---|---|---|---|
[1] General enable |
| PO 1:0 |
|
| PO 1:1 |
| |
| PO 1:13 |
| |
[1] | Selection of "Positioning" operating mode | PO 6 | 403 (decimal) |
Dynamic parameters are applied (also during ongoing movement) | PO 2 PO 3 PO 4 | Setpoint speed Acceleration Deceleration | |
[1] to [5] and from [6] | Start/stop of the axis | PO 1:7 |
|
[2] and [4] | Specification of the setpoint position (a new setpoint position is also adopted during ongoing movement) | PO 7 PO 8 | "Setpoint position" (high word) "Setpoint position" (low word) |
[1] to [2], [3] to [4] and from [7] | If the actual position lies within the configured window width, the feedback "In position" is issued. The drive stops subject to position control. When the operating mode is deselected, the signal is reset. | PI 1:7 |
|