Derating of cable length
The following table shows the values for the derating of the cable length as a function of the ambient temperature T > 40 °C:
Inverter Uline: 3 × 400 V, 3 × 500 V | Cable length |
|---|---|
Size 0S | Lnew/L = 1 - (T - 40 °C) × 5.33% at fPWM = 4 kHz Lnew/L = 1 - (T - 40 °C) × 6.7% at fPWM = 8 kHz |
Inverter Uline: 3 × 230 V | Cable length |
|---|---|
Size 0S | Lnew/L = 1 - (T - 40 °C) × 5.33% at fPWM = 4 kHz Lnew/L = 1 - (T - 40 °C) × 6.7% at fPWM = 8 kHz |
Inverter Uline: 1 × 230 V | Cable length |
|---|---|
Size 0S | Lnew/L = 1 - (T - 40 °C) × 5.33% at fPWM = 4 kHz Lnew/L = 1 - (T - 40 °C) × 6.7% at fPWM = 8 kHz |