Error 106 MOVIKIT® – Device functions
Error: 106.0 (6A00hex | 27136dec) Description: Inverter fault | ||
|---|---|---|
|
| |
Cause | Measure | |
The inverter signaled a fault but the fault number is not available to the MOVIKIT® software module. | Note the fault of the inverter as soon as it is available. Identify the exact cause of this fault and take the appropriate measures for elimination. | |
Error: 106.1 (6A01hex | 27137dec) Description: Error in communication connection to inverter | ||
|---|---|---|
|
| |
Cause | Measure | |
The inverter is not connected. | Check the EtherCAT®/SBusPLUS connection of the inverter. | |
Error restoring inverter data set (axis replacement function). | In MOVISUITE®, download the data in the parameter setting of the controller under [Data management] by clicking "Update configuration data".
| |
Error: 106.2 (6A02hex | 27138dec) Description: Inverter warning | ||
|---|---|---|
|
| |
Cause | Measure | |
The inverter signaled a warning but the warning ID is not yet available to the MOVIKIT® software module. | Note the warning of the inverter as soon as it is available. Identify the exact cause of this warning and take the appropriate measures for elimination. | |
Error: 106.32 (6A20hex | 27168dec) Description: Interface not linked | ||
|---|---|---|
|
| |
Cause | Measure | |
"DeviceHandler OSC71B" function block not passed to "CanLayer2" function block. | Pass the "DeviceHandler OSC71B" function block to the appropriate function block. | |
Error: 106.33 (6A21hex | 27169dec) Description: Timeout while sending synchronization telegram | ||
|---|---|---|
|
| |
Cause | Measure | |
A timeout occurred when sending the synchronization message. The time interval is too short. | Increase the cycle. A minimum of 2 tasks can be sent per cycle. | |
Error: 106.34 (6A22hex | 27170dec) Description: Invalid CAN ID | ||
|---|---|---|
|
| |
Cause | Measure | |
CAN identification number not valid. | Contact SEW-EURODRIVE Service. | |
Error: 106.35 (6A23hex | 27171dec) Description: Interface not linked | ||
|---|---|---|
|
| |
Cause | Measure | |
Logical device not passed to initialization method (INIT) of "DeviceHandler OSC71B" function block. | Pass the logical device to the "DeviceHandler OSC71B" function block. | |
"DeviceHandler OSC71B" function block not passed to the initialization method (INIT) of the "CanOpen", "SBusProcessData" or "SBusParameter" function blocks. | Pass the "DeviceHandler OSC71B" function block to the appropriate function block. | |
Error: 106.36 (6A24hex | 27172dec) Description: Lower-level CAN station error | ||
|---|---|---|
|
| |
Cause | Measure | |
Error detected in the "DeviceHandler" function block of the lower-level CAN station. | Observe the status message of the logical device. Identify the exact cause of this status message and take the appropriate measures for elimination. | |
Error: 106.37 (6A25hex | 27173dec) Description: CAN data memory not linked | ||
|---|---|---|
|
| |
Cause | Measure | |
Internal error | Contact SEW-EURODRIVE Service. | |
Error: 106.38 (6A26hex | 27174dec) Description: CAN interface not ready | ||
|---|---|---|
|
| |
Cause | Measure | |
The CAN interface is initialized (INIT state). | Check the cabling and the DIP switch settings of the OSC71B option card. | |
Error: 106.39 (6A27hex | 27175dec) Description: CAN station at CAN interface not ready | ||
|---|---|---|
|
| |
Cause | Measure | |
Error detected in the "DeviceHandler" function block of the CAN station. | Observe the status message of the logical device. Identify the exact cause of this status message and take the appropriate measures for elimination. | |
Error: 106.40 (6A28hex | 27176dec) Description: Not initialized | ||
|---|---|---|
|
| |
Cause | Measure | |
Initialization method (INIT) completed with errors. | Call the initialization method again. The return value "SEW_IDAOSC.E_OscError.eOk" is returned after successful initialization. | |
Error: 106.41 (6A29hex | 27177dec) Description: CAN ID already assigned | ||
|---|---|---|
|
| |
Cause | Measure | |
CAN identification number assigned several times. | Check CAN addresses and CAN IDs. | |
Error: 106.42 (6A2Ahex | 27178dec) Description: Invalid CAN address | ||
|---|---|---|
|
| |
Cause | Measure | |
CAN address not within permitted address range. | Set the CAN address in the address range 1 – 127. | |
Error: 106.43 (6A2Bhex | 27179dec) Description: Large number of process data objects | ||
|---|---|---|
|
| |
Cause | Measure | |
Too many process data objects created. | For the permitted number of process data objects, refer to the global variable "SEW_IDAOSC.GVL_CanOpen.gc_uiMaxNumberOfPDO". | |
Error: 106.44 (6A2Chex | 27180dec) Description: Timeout while sending send telegram | ||
|---|---|---|
|
| |
Cause | Measure | |
A timeout occurred when sending the send telegram. The telegram runtime is too large. | Increase the timeout. | |
Error: 106.45 (6A2Dhex | 27181dec) Description: Parameter request timeout | ||
|---|---|---|
|
| |
Cause | Measure | |
Timeout during parameter request of the "ServiceDataObject" service. The telegram runtime is too large. | Increase the timeout. | |
Error: 106.46 (6A2Ehex | 27182dec) Description: Timeout while sending heartbeat telegram | ||
|---|---|---|
|
| |
Cause | Measure | |
A timeout occurred when sending the heartbeat telegram. The telegram runtime is too large. | Increase the timeout. | |
Error: 106.47 (6A2Fhex | 27183dec) Description: Emergency telegram from CAN station | ||
|---|---|---|
|
| |
Cause | Measure | |
CAN station detected error and sent emergency telegram. | Exact data from the emergency telegram can be found in the logbook in the IEC Editor. For further information about the emergency telegram, refer to the documentation of the CAN axis group member. | |
Error: 106.48 (6A30hex | 27184dec) Description: Parameter request error | ||
|---|---|---|
|
| |
Cause | Measure | |
An error was detected during the parameter request of the "ServiceDataObject" service. Access to parameters in CAN axis group member not allowed. | Observe the AbortCode on the block. Identify the exact cause of this AbortCode and take the appropriate measures for elimination. For further information about the AbortCode, refer to the documentation of the CAN axis group member. | |
Error: 106.49 (6A31hex | 27185dec) Description: Parameter request error | ||
|---|---|---|
|
| |
Cause | Measure | |
Error detected during the parameter request. The telegram runtime is too large. | Increase the timeout. | |
Error: 106.50 (6A32hex | 27186dec) Description: MOVILINK® parameter request error | ||
|---|---|---|
|
| |
Cause | Measure | |
Access to parameter in CAN station not allowed. | Observe the AbortCode on the block. Identify the exact cause of this AbortCode and take the appropriate measures for elimination. For further information about the AbortCode, refer to the documentation of the CAN axis group member. | |
Error: 106.51 (6A33hex | 27187dec) Description: MOVILINK® parameter request timeout | ||
|---|---|---|
|
| |
Cause | Measure | |
Timeout during the MOVILINK® parameter request. The telegram runtime is too large. | Increase the timeout. | |
Error: 106.52 (6A34hex | 27188dec) Description: Invalid MOVILINK® process data length | ||
|---|---|---|
|
| |
Cause | Measure | |
Process data length not set correctly. | Set the process data length to a value > 0 and < 16. | |
Error: 106.53 (6A35hex | 27189dec) Description: Invalid MOVILINK® process data segment | ||
|---|---|---|
|
| |
Cause | Measure | |
Internal error | Contact SEW-EURODRIVE Service. | |