General settings for connection types A and B

The following settings are required for connection type A and connection type B.

Configure the voltage supply in the parameterization of the inverter under [Drive trains] > [Drive train 1] > [Controller]:

Proceed as follows:

  1. In the Voltage supply parameter, select the setting "Grid directly".
  2. In the AC nominal voltage parameter, enter the voltage of the AC grid.
  3. Activate the DC link connection parameter.
  4. In the Application limitApparent output current parameter, enter the value that is specified by the overload capacity (see Overload capacity).