General settings for connection types A and B
The following settings are required for connection type A and connection type B.
Configure the voltage supply in the parameterization of the inverter under [Drive trains] > [Drive train 1] > [Controller]:
Proceed as follows:
- In the Voltage supply parameter, select the setting "Grid directly".
- In the AC nominal voltage parameter, enter the voltage of the AC grid.
- Activate the DC link connection parameter.
- In the Application limit – Apparent output current parameter, enter the value that is specified by the overload capacity (see Overload capacity).