Line connection

For the terminal assignment for line connection, refer to chapter "Terminal assignment".

Observe a minimum switch-off time of 10 s for the power supply module. Do not switch the power on or off more than once per minute.

NOTICE

Non-compliance with the minimum switch-on/switch-off times.
Adhere to the specified times and intervals.
  • Observe the minimum switch-off time of 10 s before switching the power back on.
  • Do not switch the power of the supply system on or off more than once per minute.
  • The line contactor must always be located upstream of the line filter.
  • Use only line contactors of utilization category AC-3 (EN 60947-4-1) or higher.
  • Do not use the line contactor for jog mode, but only for switching the power supply module on and off. The FCB 20 "Jog" must be used for jog mode.
  • Observe the required dimensioning of the cable cross-section for UL-compliant installation.