Fault 1 Output stage monitoring

Subfault: 1.2

Description: Overcurrent in output stage

 

Response: Output stage inhibit + line contactor unchanged + module bus response "Critical"

Cause

Measure

Motor current too high.

Connect a smaller motor.

Current supply

Check the current supply.

Current transformer

Check the current transformer.

Ramp limit deactivated and set ramp time too short.

Increase the ramp time.

Phase module defective.

Check the phase module.

DC 24 V supply voltage unstable.

Check the DC 24 V supply voltage.

Interruption or short circuit on signal lines of phase modules.

Check the signal lines.