NDR.. step-up choke
NOTICE
Use non-magnetic fasteners
The step-up choke may only be secured in place with non-magnetic screws.
Bear in mind that the NDR1100-501 step-up choke is a single-phase choke that must be installed 3 times. Each phase between the line choke and the supply and regenerative module must be connected via a step-up choke.
The NDR1100-501 or NDR0750-503 step-up chokes must be connected to the filter module using a cable with a cross-section of 6 mm² each. A maximum of 16 mm² can be connected to the step-up choke and the filter module.