Smallest wire bending space (EN 61800‑5‑1)
As stipulated in EN 61800-5-1, the distance between a power connection terminal and an obstruction toward which the wire is directed on leaving the terminal must correspond with the minimum values given in the table below.
Cable cross section in mm2 | Smallest wire bending space in mm | ||
---|---|---|---|
Wires per connection terminal | |||
1 | 2 | 3 | |
10 – 16 | 40 | – | – |
25 | 50 | – | – |
35 | 65 | – | – |
50 | 125 | 125 | 180 |
70 | 150 | 150 | 190 |
95 | 180 | 180 | 205 |
120 | 205 | 205 | 230 |
150 | 255 | 255 | 280 |
185 | 305 | 305 | 330 |