SS1(c) Safe Stop 1 (EN 61800-5-2)

The procedure is as follows:

  • X12:1 must not be disconnected.
  • X12:4 is disconnected, e.g. in case of an emergency stop.
  • During the safety time interval t1, the motor decelerates to a complete stop along the ramp.
  • After t1 has elapsed, the safety input X7 is disconnected. The safe time t1 must be sufficient for the motor to reach a complete stop.

INFORMATION

  • The illustrated SS1(c) disconnections can be used up to PL d according to EN ISO 13849-1:2015 taking account of the chapter "Requirements".
  • ®  size 0 requires an external DC 24 V voltage supply.