Switched inductances
CAUTION
Switched inductances
Hazard: Malfunctions / damage to property.
- The minimum distance of switched inductances to the inverter must be at least 150 mm (5.91 in).
- Use suppressors to suppress interference on
- Contactors
- Relays
- Solenoid valves
- Suppressors are, for example, diodes, varistors, or RC elements:
Do not connect any suppressors directly to MOVITRAC® B. Connect suppressors as closely as possible to the inductance.