P112 AI1 Operating mode
P112 AI1 Operating mode
1 / 10 V, reference maximum speed
Voltage input with reference nmax (0 – 10 V = 0 – nmax). You can adjust the characteristic curve with AI1 Scaling.
Switch S11 = V.
5 / 0 – 20 mA, reference maximum speed
Current input 0 – 20 mA = 0 – nmax. P110 AI1 scaling has no effect.
Switch S11 = mA.
6 / 4 – 20 mA, reference maximum speed
Current input 4 – 20 mA = 0 – nmax. P110 AI1 scaling has no effect.
Switch S11 = mA.
7 / 0 – 10 V, n-reference
8 / 0 – 20 mA, n-reference
9 / 4 – 20 mA, n-reference