Parameter settings
The following parameters have to be set in MOVITRAC® B other than the factory setting. When you use a FBG11B for setting the parameters, set the values indicated in parenthesis:
- P100 Setpoint source: RS485 (2)
- P101 Control signal source: RS485 (1)
- P871 Setpoint description PO2: Set PO2 to "Speed %", then P876 PO data enable to "Yes".
The speed is now displayed: –100% to +100% correspond to –nmax to +nmax.