Control functions
Parameter designation | Description |
|---|---|
Application heartbeat | |
Timeout | If communication between the MOVI-C® CONTROLLER and the lower-level members is interrupted for the set time, the members stop with the specified fault response. The fault response is defined in the member under [Functions] > [Monitoring functions] > [Overview of fault responses] in the parameter "Response timeout application heartbeat" (index 8622.21) and executed at a timeout time >0. Default value: 0.2s |
Monitoring window | |
Lag error window | Window of the actual lag error (in user units). No lag error is created when the setting is "0". Default value: One motor rotation (in user unit) |
Index: 50012.03 | |
IEC name: Controller.PositionController.Config.lrLagErrorWindow | |
Skew error window | Position window for the permitted skew error between the axis group members (in user units). If this window is exceeded, a fault will be issued and the set fault response will be performed. Default value: |
Index: 50011.24 | |
IEC name: Controller.MAC.Config.SkewLeveling.lrSkewErrorWindow | |
Skew window | Position window for current skew. If this is within the window, Controller.MAC.Out.SkewLeveling.xInSkewWindow or PI 10:10 is set. Default value: |
Index: 50011.26 | |
IEC name: Controller.MAC.Config.SkewLeveling.lrSkewWindow | |