Establishing the network connection
Proceed as follows:
- Establish a physical connection between the engineering PC and the controller.
- Configure the interfaces of the engineering PC and the controller so that they are in a common network. The standard engineering interface X80 of the MOVI-C® CONTROLLER has the following IP address parameters in the delivery state:
- IP address: 192.168.10.4
- Subnet mask: 255.255.255.0
INFORMATION

SEW‑EURODRIVE recommends using the standard engineering interface for startup.
As soon as the project on the controller has reached a stable state, e.g. when regular updates and downloads of the IEC project are no longer required, the PROFINET/PROFIsafe interface can be used for engineering. If already known, assign the correct IP address in the IEC project in the properties of the fieldbus station.
- Use the "ping IP address of controller" command in the Windows command prompt to check whether there is a communication connection to the controller.