Connecting explosion-protected AC motors

Observe the following information:

  • Install the inverter outside the potentially explosive atmosphere.
  • Observe industry and country-specific regulations.
  • Observe the regulations and information of the motor manufacturer with regard to operation on a frequency inverter, e.g. mandatory sine filter.
  • All operating resources used in potentially explosive atmospheres must adhere to the relevant standards, such as Directive 2014/34/EU or IEC 60079.
  • In connection with the HV brake control /B, the brake control must be set to "voltage control" because choppers in the brake coil is not permitted.
  • The sensor input of the motor's temperature monitoring must not be used in potentially explosive atmospheres. For thermal monitoring, use a monitoring device approved for potentially explosive atmospheres.
  • In case of motors with speed feedback, the speed sensor must also be approved for potentially explosive atmospheres. The speed sensor can be directly connected to the inverter.

INFORMATION

For further information, refer to the associated catalogs and the operating instructions of the explosion-protected motors.