Single- or multi-stage fuse concept (MultipleFuseControl)
HEX | DC | Error response | Meaning | Cause | Solution |
|---|---|---|---|---|---|
16#9040 | 36928 | Error message + emergency stop (10) | No device IOs have been configured for the function. In addition, no IOConnector FB is linked so that the function cannot read inputs or set outputs. |
|
|
16#9041 | 36929 | Immediate energy storage disconnection (30) | Relay is stuck. |
| Replace the relay. |
16#9042 | 36930 | Immediate energy storage disconnection (30) | Timeout when switching the relay: Requested switching was not performed. |
| Replace the relay. |
16#9043 | 36931 | Immediate energy storage disconnection (30) | Fuse has high impedance (destroyed) |
| Replace defective fuses. |
16#9044 | 36932 | Error message + emergency stop (10) | "Limit of current limiting off" is greater than "Limit of current limiting on". | The voltage limits are configured incorrectly. The "Current limiting off" switching threshold must be greater than the "Current limiting on" switching threshold. | Adjust the limits in MOVISUITE® accordingly and then update the configuration data of the project. |