Decoding the read parameter values

 

Error code

Subfault code

Value read

0x2D03

Bit mask: Bit 8 – 15

0xFF00

 

Bit mask: Bit 0 – 7

 

0x00FF

Error code.Sub-error code

hexadecimal representation:

decimal representation:

 

0x2D

45

 

0x03

03

In this example, the error E-45.03 Fieldbus interface: Process output data timeout was triggered on the inverter.

Error: 45.3

Description: Process output data timeout

 

Response: Fieldbus – timeout response

Cause

Measure

Timeout in process data transfer during fieldbus communication.

– Check the communication connection between the fieldbus master and the fieldbus interface for interruption.

– Check the configuration of the fieldbus master.

– Adjust the timeout monitoring of the fieldbus interface.

For an error list and descriptions of other errors, refer to the operating instructions of the respective inverter.