Decoding the read parameter values
| Error code | Subfault code |
|---|---|---|
Value read | 0x2D03 | |
Bit mask: Bit 8 – 15 | 0xFF00 |
|
Bit mask: Bit 0 – 7 |
| 0x00FF |
Error code.Sub-error code hexadecimal representation: decimal representation: |
0x2D 45 |
0x03 03 |
In this example, the error E-45.03 Fieldbus interface: Process output data timeout was triggered on the inverter.
Error: 45.3 Description: Process output data timeout | ||
|---|---|---|
| Response: Fieldbus – timeout response | |
Cause | Measure | |
Timeout in process data transfer during fieldbus communication. | – Check the communication connection between the fieldbus master and the fieldbus interface for interruption. – Check the configuration of the fieldbus master. – Adjust the timeout monitoring of the fieldbus interface. | |
For an error list and descriptions of other errors, refer to the operating instructions of the respective inverter.