DIP switch S1/3: Deactivating the speed monitoring
INFORMATION
If the function of this DIP switch is deactivated via parameter access, the last active setting of the relevant parameter is maintained.
This DIP switch is used to disable speed monitoring.
- Speed monitoring OFF (S1/3 = ON): Speed monitoring is not active.
- Speed monitoring ON (S1/3 = OFF): Speed monitoring is active.
- Speed monitoring is used to protect the drive in case of blockage.
- When speed monitoring is active and the drive operates at the current limit for longer than 1 second (factory settings), the drive unit triggers the fault "Speed monitoring". The drive unit signals the fault, for example via the "DRIVE" status LED. The current limit must be reached permanently for the duration of the delay time before the monitoring function trips.