Fault 23 Power section

Subfault: 23.4

Description: Hardware error

 

Response: Output stage inhibit

Cause

Measure

Fault detected in a hardware component of the power section.

– Check for short circuit / ground fault at the output of the inverter.

– Reduce the line capacity at the output of the inverter.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Fault detected on switched-mode power supply.

Check the DC 24 V supply voltage.

Error detected at the gate driver of a power semiconductor.

Contact SEW‑EURODRIVE Service.