State of charge control

HEX

DEC

Error response

Meaning

Cause

Solution

16#9101

37121

Error message

+ emergency stop (10)

Switching state of storage unit is unknown. FCB request with output stage enable is not issued.

The current error is a consequential error. The switching state of the storage unit is unknown if DC synchronization has not yet been worked or if an error has been detected there.

Select the "DC synchronization" operating mode again, connect or disconnect the storage unit, and rectify any errors that may have occurred.

16#9102

37122

Error message

+ emergency stop (10)

The voltage limits of state of charge control (StateOfChargeControl) are inconsistent.

The configured voltage limits of state of charge control are invalid.

Correctly parameterize voltage limits according to project planning or operating instructions.

16#9103

37123

Warning message

The voltage limits of state of charge control (StateOfChargeControl) are inconsistent.

Configured voltage limits of state of charge control are invalid but do not restrict operation.

Correctly parameterize voltage limits according to project planning or operating instructions.