Status (OUT)

Variable name

Description

xConnected

Data type – BOOL

  • TRUE – Communication connection (SBusPLUS) active
  • FALSE – Communication connection (SBusPLUS) not active

eInverterMode

 

INFORMATION: The listed storage unit FCBs (FCB 6X) are not used by the software module. Storage management runs completely on the MOVI-C® CONTROLLER.

Data type – ENUMERATION

Active FCB or active operating mode.

  • FCB00_DEFAULT: 0
  • Default FCB
  • FCB51_POWER_STAGE_INHIBIT: 51
  • Output stage inhibit activated
  • FCB52_BRAKE_CHOPPER_INHIBIT: 52
  • Brake chopper blocked due to fault
  • FCB55_VOLTAGE_CONTROL: 55
  • DC link voltage control activated
  • FCB57_CURRENT_CONTROL: 57
  • Control of input current activated
  • FCB59_CURRENT_TRACKING_CONTROL: 59
  • Current sequence control is active
  • FCB61_IDLE_LEVEL_CONTROL: 61
  • State of charge control
  • FCB64_DETACH_STORAGE: 64
  • Disconnect storage unit

wDigitalInputs

Data type – WORD

State of the digital inputs

Information: Depending on the software module used, digital inputs are already reserved and cannot be used.

usiErrorID

Data type – USINT

Error ID

usiErrorSubID

Data type – USINT

Suberror ID

xLimitActive

Data type – BOOL

  • TRUE – An internal limit is active and limits the setting range of the device
  • FALSE – The device operates within its setting range

xPowered

Data type – BOOL

  • TRUE – The output stage of the device is enabled
  • FALSE – The output stage of the device is inhibited

xReady

Data type – BOOL

  • TRUE – The device is ready for operation
  • FALSE – The device is not ready for operation

xSetpointActive

Data type – BOOL

  • TRUE – Setpoints are processed
  • FALSE – Setpoints are not processed

xSetpointReached

Data type – BOOL

  • TRUE – Specified setpoint is reached
  • FALSE – Specified setpoint is not reached

xStandByActive

Data type – BOOL

  • TRUE – Standby mode activated
  • FALSE – Standby mode deactivated