Interference emission
The cable length must be as short as possible for EMC-compliant installation.
SEW‑EURODRIVE recommends using low-capacity cables.
To comply with limit classes C1, C2, and C3 in accordance with EN 61800‑3, take the measures listed in the tables.
Limit class C1
Inverter | Measures | |
---|---|---|
On the line side | On the motor side | |
CNF... line filter | Shielded cables | |
MCB91A-xxxx-2D1-... | CNF... | Yes |
Limit class C2
Inverter | Measures | |
---|---|---|
On the line side | On the motor side | |
CNF... line filter | Shielded cables | |
MCB91A-... | CNF... | Yes |
Limit class C3
Inverter | Measures | |
---|---|---|
On the line side | On the motor side | |
CNF... line filter | Shielded cables | |
MCB91A-... | No | Yes |