Subsequent activation of axis simulation

 

 

Problem

The IEC program no longer starts properly if a simulation is activated for individual axes in a project for which configuration data and inverter data sets are already present on the memory card.

The IEC program fails to recognize the inverter data sets and attempts to transfer them to the axes. As the axes cannot be accessed, the MOVI‑C® CONTROLLER signals a fault and the IEC program does not start properly.

Remedy
  1. Remove the memory card from the MOVI‑C® CONTROLLER
  2. Delete the content of the folder named ".\backup\devices".
  3. INFORMATION

    Do NOT delete the "backup" folder. The backup folder is an essential part of the image.
  4. Insert the memory card into the MOVI‑C® CONTROLLER again.
  5. Switch on the MOVI‑C® CONTROLLER again.
  6. In MOVISUITE®, perform the function "Update IEC project".