Digital outputs

Unit

Specification

Number

–

4

Design

–

in accordance with IEC 61131-2

Response time

µs

175 plus cycle time

Maximum output current

mA

50, protection circuit required for inductive load
(e.g. freewheeling diode or varistor)

Capacitive load

nF

≤ 300

Inductive load

–

Not permitted

Protection device

–

Short-circuit proof, protected against external voltage DC 0 – 30 V

X52:6 – 9

–

DO10 – DO13: Selection option, see parameter menu