Error 7 DC link
Error: 07.01 (0701hex | 1793dec) Description: DC link overvoltage | ||
|---|---|---|
| Response: Output stage inhibit | |
Cause | Measure | |
Maximum permitted DC link voltage limit exceeded. | – Check the connection of the braking resistor. – Decrease deceleration. – Check the configuration of the braking resistor (resistance value). | |
Error: 07.02 (0702hex | 1794dec) Description: DC link discharge failed | ||
|---|---|---|
| Response: Warning | |
Cause | Measure | |
DC link voltage level not dropped below discharge threshold within discharge time. | Contact SEW-EURODRIVE Service. | |