Error 51 Analog processing

Error: 51.01 (3301hex | 13057dec)

Description: Current at analog current input too small

 

 

Cause

Measure

Input current at analog input below 4 mA.

– Check the wiring.

– Check the parameterization of the analog input.

Error: 51.02 (3302hex | 13058dec)

Description: Voltage/current changeover faulty

 

 

Cause

Measure

The hardware configuration for switching between voltage input and current input on the basic unit does not match the parameterization of the analog input.

– Check the position of the switch for the current/voltage configuration

or