ELSM®
The ELSM® control mode enables operation of permanent-field synchronous motors without an encoder.
Make sure that the inverter can deliver at least 150% I0 of the motor.
Switching to a rotating motor is possible (flying start function). Continuous operation is only permitted above a transition speed of approx. 2% of the nominal motor speed.
Additional information