Error 83 Sensor

Error: 83.1 (5301hex | 21249dec)

Description: Unknown sensor

 

 

Cause

Measure

The connected sensor is not known to the device.

– Check wiring and type of sensor.

– Update the firmware of the device that supports the connected sensor.

Error: 83.2 (5302hex | 21250dec)

Description: Wiring error

 

 

Cause

Measure

Connected sensor not wired correctly.

Check the wiring.

Error: 83.3 (5303hex | 21251dec)

Description: Communication error

 

 

Cause

Measure

Faulty or incomplete telegrams received via communication line.

– Check wiring of the sensor.

– Check susceptibility to faults.

Error: 83.4 (5304hex | 21252dec)

Description: Communication interrupted

 

 

Cause

Measure

Communication has been interrupted:

– No telegrams are being received.

– The timeout time has expired.

– Check wiring of the sensor.

– Ensure that the sensor is fully functional.

Error: 83.5 (5305hex | 21253dec)

Description: Defective sensor

 

 

Cause

Measure

Sensor signaled internal malfunction (e.g. via communication line).

Replace the sensor.

Error: 83.6 (5306hex | 21254dec)

Description: Sensor system boot error

 

 

Cause

Measure

The sensor does not boot properly. Sensor is connected and detected but does not respond.

Check the sensor wiring. If the sensor is defective, replace it.

Error: 83.7 (5307hex | 21255dec)

Description: Error in the process data communication

 

 

Cause

Measure

Process data communication with sensor disrupted or interrupted.

Check cabling to the sensor. Replace defective sensor if necessary.