Minimum clearance and mounting position

Observe the following information:

  • To ensure unobstructed cooling, leave a minimum clearance of 100 mm above and below the inverter housings. Ensure that the air circulation in this clearance is not impaired by cables or other installation equipment.
  • Make sure that the inverters are not exposed to the exhaust air from other units.
  • Only install the inverters vertically. Do not install them horizontally, tilted, or upside down.
  • Lateral clearance is not required. The units can be arranged directly next to one another.

INFORMATION

Observe the bending spaces in accordance with EN 61800-5-1.