Ambient temperature

The units are suitable for an ambient temperature of 40 °C, max. 60 °C with derated output current.

 

MOVIDRIVE® MDR60A..: To determine the output current rating at higher than 40 °C, the output current should be derated 3% per °C between 40 °C and 60 °C.

HINWEIS

Use only certified devices with a limited output voltage (Vmax = DC 30 V) and limited output current (Imax = 8 A) as an external DC 24 V voltage source.
UL approval does not apply to operation in voltage supply systems with a non-earthed star point (IT systems).