Diagnostics
The following energy storage unit statuses change the behavior of the MOVIKIT® StackerCrane effiDRIVE. During troubleshooting, both the status of the power supply module and the status of the MOVIKIT® StackerCrane effiDRIVE should be observed.
Energy storage unit | Resulting | Power supply module | IEC variable |
|---|---|---|---|
MOVIKIT® PowerMode connected to MOVIKIT® StackerCrane effiDRIVE | MOVIKIT® StackerCrane effiDRIVE responds according to this table | – | SEW_GVL_Internal.StackerCrane.fbX._stPowerMode.xConnectedToStackerCrane |
During run-up: | Wait in emergency stop | 14 | SEW_GVL_Internal.StackerCrane.fbX. |
Storage unit error: | Controller inhibit | 1 | SEW_GVL_Internal.StackerCrane.fbX. |
MOVIKIT® PowerMode error | Emergency stop | (6 / 10) 14 | SEW_GVL_Internal.StackerCrane.fbX. |
Storage unit disconnected | Reduced | According to control on the MOVIKIT® StackerCrane effiDRIVE | SEW_GVL_Internal.StackerCrane.fbX. |