Fault 32 Communication

Fault: 32.1 (2001hex | 8193dec)

Description: CBus communication timeout

 

 

Cause

Measure

A timeout occurred in the process data transfer during communication via the CBus communication option.

– Check the wiring of the system bus.

– Make sure that the communication option is set correctly.

– Check the set timeout time of the CBus communication option.

Fault: 32.2 (2002hex | 8194dec)

Description: EtherCAT®/SBusPLUS communication timeout

 

 

Cause

Measure

Timeout in process data transfer during EtherCAT®/SBusPLUS communication.

– Check the wiring of system bus and module bus.

– Make sure that the EtherCAT®/SBusPLUS configuration in the controller is set correctly.

– Check the set timeout time of the EtherCAT®/SBusPLUS interface.

Fault: 32.3 (2003hex | 8195dec)

Description: Faulty synchronization signal

 

 

Cause

Measure

Synchronization signal period is not correct.

Make sure that the EtherCAT®/SBusPLUS configuration in the controller is set correctly.

Fault: 32.4 (2004hex | 8196dec)

Description: Missing synchronization signal

 

 

Cause

Measure

No synchronization signal present.

Make sure that the EtherCAT®/SBusPLUS configuration in the controller is set correctly.

Fault: 32.5 (2005hex | 8197dec)

Description: Synchronization timeout

 

 

Cause

Measure

Timeout while synchronizing to synchronization signal.

Make sure that the EtherCAT®/SBusPLUS configuration in the controller is set correctly.

Fault: 32.6 (2006hex | 8198dec)

Description: Error while transferring parameter set

 

 

Cause

Measure

Error while downloading parameter set to device.

– Check the wiring of system bus and module bus.

– Restart the transfer.

Fault: 32.7 (2007hex | 8199dec)

Description: Application heartbeat timeout

 

 

Cause

Measure

Communication between the application program (e.g. IEC program or MOVIKIT® from the Drive category) and the device was interrupted.

– Check the status of the application program.

– Restart the application program.

Fault: 32.8 (2008hex | 8200dec)

Description: User-timeout timeout

 

 

Cause

Measure

The timeout time of the user timeout function has expired.

– Check communication.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Fault: 32.11 (200Bhex | 8203dec)

Description: Local mode timeout

 

 

Cause

Measure

Communication connection to device interrupted in local mode.

Increase the timeout setting in local mode.

New Scope project created.

– Reset the fault.

– Start local mode again.

Scope measurement loaded from device.

– Reset the fault.

– Start local mode again.

Fault: 32.12 (200Chex | 8204dec)

Description: Manual mode timeout

 

 

Cause

Measure

Communication connection to inverter interrupted in manual mode.

– Check whether too many programs are open on the engineering PC.

– Increase the timeout time in manual mode.

New Scope project created.

– Acknowledge the fault.

– Restart manual mode.

Scope measurement transferred from inverter to project.

– Acknowledge the fault.

– Restart manual mode.

Fault: 32.13 (200Dhex | 8205dec)

Description: Process data timeout

 

 

Cause

Measure

Timeout in the process data transfer.

– Switch the devices off and on again.

– If the fault occurs repeatedly, contact SEW‑EURODRIVE Service.

Fault: 32.14 (200Ehex | 8206dec)

Description: Internal communication error

 

 

Cause

Measure

An error occurred in internal communication.

– Switch the device off and on again.

– If the fault occurs repeatedly, replace the safety option and send it together with the fault number to SEW‑EURODRIVE. For further support, contact SEW‑EURODRIVE Service.

Fault: 32.15 (200Fhex | 8207dec)

Description: Error due to configuration change

 

 

Cause

Measure

The CAN interface setting has been changed.

Acknowledge the fault and restart the firmware.

Fault: 32.16 (2010hex | 8208dec)

Description: CBus PE data timeout

 

 

Cause

Measure

One or more stations on the CBus no longer respond.

– Check CBus cabling.

– Check whether CBus axis group members are switched on.