X4108: CAN bus – system bus
INFORMATION

If there is no station connected here, you must terminate the bus with a 120 Ω resistor.
Function |
|---|
CAN system bus – input |
Connection type |
|---|
M12, 5-pin, male, A-coded |
Connection diagram |
|---|
|
Assignment | ||
|---|---|---|
Contact | Function | |
1 | CAN_SHLD | Shield/equipotential bonding CAN bus |
2 | res. | Reserved |
3 | GND | Reference potential |
4 | CAN_H | CAN data line (high) |
5 | CAN_L | CAN data line (low) |
Additional information