Fault 35 Function activation

Fault: 35.1 (2301hex | 8961dec)

Description: Activation level – invalid activation key

 

Response: Emergency stop + output stage inhibit

Cause

Measure

Activation key not entered properly.

Enter the activation key again.

Activation key not created for this device.

Check the activation key.

For a double-axis, the activation key of the wrong instance was entered in the device.

Enter the activation key for the assigned instance.

Activation key entered for technology level in parameter "Application level – activation key".

Enter the activation key in the correct parameter.

Fault: 35.2 (2302hex | 8962dec)

Description: Application level too low

 

Response: Emergency stop + output stage inhibit

Cause

Measure

The activated software module requires a higher application level.

Determine the required application level ("Application level – required level" parameter) and enter its activation key.

Fault: 35.3 (2303hex | 8963dec)

Description: Technology level too low

 

Response: Emergency stop + output stage inhibit

Cause

Measure

An activated technology function requires a higher technology level.

Determine the required technology level ("Technology level – required level" parameter) and enter its activation key.

Fault: 35.4 (2304hex | 8964dec)

Description: Technology level – invalid activation key

 

Response: Emergency stop + output stage inhibit

Cause

Measure

Activation key not entered properly.

Enter the activation key again.

Activation key not created for this device.

Check the activation key.

For a double-axis, the activation key of the wrong instance was entered in the device.

Enter the activation key for the assigned instance.

Activation key entered for application level in parameter "Technology level – activation key".

Enter the activation key in the correct parameter.