Use of safety controllers
The switch-off test pulse of the used safe digital outputs (F-DO) must be ≤ 1 ms and another switch-off test pulse must only occur 2 ms later at the earliest.

[1] | High |
[2] | Low |
INFORMATION

If the safety-related control voltage at X6 is switched off (STO activated), you must observe the chapter "Requirements for the external safety controller" with regard to the test pulses.