Inrush current limiter
HEX | DEC | Error response | Meaning | Cause | Solution |
|---|---|---|---|---|---|
16#9160 | 37216 | 10 | The output stage side to which the energy storage unit is connected has not been selected in the device. | Error in parameter communication with MOVISUITE®. | Update configuration data. |
16#9161 | 37217 | 10 | The IO channel to the relay and the fuse contact is missing. | No IOs configured. | Connect standard or external IOs. |
16#9162 | 37218 | 30 | Precharging error | The voltage above the precharging resistor does not drop or drops too slowly. | Check the impulse series relay. |
16#9163 | 37219 | 30 | Relay fault | The impulse series relay is open although it should be closed. | Check the impulse series relay. |