Example 2

[1]

Drive unit

[2]

External safety device

Observe the following notes:

  • The supply voltages 0V24_OUT and 24V_OUT must not be used to supply the external safety device.
  • This connection variant (example 2) is only permitted if a fault can be excluded for the cable between the drive unit and the external safety device. Fault exclusion between any 2 conductors in a cable according to EN ISO 13849-2 is possible if the cable is permanently (fixed) installed and protected against external damage, for example, by using cable duct or armored conduit.