Example 2
[1] | Drive unit |
[2] | External safety device |
Observe the following notes:
- The supply voltages 0V24_OUT and 24V_OUT must not be used to supply the external safety device.
- This connection variant (example 2) is only permitted if a fault can be excluded for the cable between the drive unit and the external safety device. Fault exclusion between any 2 conductors in a cable according to EN ISO 13849-2 is possible if the cable is permanently (fixed) installed and protected against external damage, for example, by using cable duct or armored conduit.